Friday 5 August 2016

inverter,s the constant in the grey place only exits in v c.





the constant in the grey place only exits in   v c.

frequency reference
monitoring and setting of frequency reference value.
the display units can be set with user constant o1-03
output frequency
monitors the output frequency the display units can be set with user constant o1-03


output current
monitors the output current 10 v : rated current(0 to + 10 volts output)
control method
shows which control mode is set can not be output
motor speed
monitors the motor speed. the display unit setting   
can be changed by o 1 - 03 output signal levels for
function analog outputs 10 volts : max . frequency  
(0 to _+  volts possible ) and min unit is 0.01 hz     
and valid access levels v/f is x v/f w/pg is q and      
open loop vector is q and flux vector is q.              

output voltage.
monitors the inverters  internal output voltage refer
ence value.output signal levels for function analog  
outputs 10 voltage :ac 200 v (ac 400)(0-+10 v     
output)and min unit is 1v and v/f is q and v/f w/pg 
is q and open loop vector is q and flux vector is q.


Monday 18 July 2016

INVERTER,S DRIVING MODE .

driving mode.
driving mode is the operation mode of inverter.
in the different access levels' the constant which can
be adjusted (the constant can be adjusted online)
will be limited. the constants which can be adjusted
and the ones which can not be adjusted are dis ding
shed by x and 0 in the constant table. in the status of driving mode' frequency command' output frequency
output current'output voltage and other constants can be monitored and the abnormal content and records can be displayed by the operator's screen.






Sunday 10 July 2016

INVERTER,S FREQUENCY COMMAND AND OPERATION COMMAND SELECTION

frequency command selection.
0: frequency command is mainly set by operator (d 1 - 0 1) ref off.
1:frequency command is mainly set by exterior terminal 13' 14 ref on flickering .
2:frequency command is mainly set by communication ref flickering.
3: frequency command is mainly set by interface card.

operation command selection.
0: operation command is mainly set by operator seq off.
1: command is mainly set by exterior terminal seq on.
2: command is mainly set by communication seq flickering.
3: command is mainly set by interface card seq flickering.

to execute trial operation by operator.
this section describes the motors trial operation by operator
without load.
the input frequency is set in the operating status.the operation
is example with input frequency'20 h z.





Friday 8 July 2016

INVERTER,S TRAIL OPERATION OF INVERTER VC.

CHECK POINTS BEFORE OPERATION

to check the inverter and get familiar with the operation 'please make trial operation before formal operation.
please confirm the following before operation.
wiring is correct or not. terminal screw is fastened or not.wiring is proper or cable is damaged or not load status is correct or not.










CHECK POINTS IN OPERATION.

motor operation is smooth or not. motor operation direction is correct or not motor has abnormal vibration or not. deceleration/acceleration is smooth or not. load current ie beyond the permitted range or not operator's display is correct or not.

OPERATOR TRIAL OPERATION.

the operation of inverter has 2 kinds operation modes' local and remote. the factory default is remote (control circuit terminal command is effective) ' the constant content is as follows:  local: frequency and operation command are input by operator. seq and ref indicator will be off.
remote: frequency and operation command are input by exterior terminal' seq and ref indicator will be on.
  



           

Thursday 7 July 2016

THE INITIALIZATION OF VC SERIES.

  THE INITIALIZATION OF VC SERIES.

initialization is to reset the value to be factory default. al-03 is used to change the factory default.
note:   after each operation of factory default reset'the carrier frequency need to be set again. otherwise' the inverter could be
damaged. the inverter with different capacity shell have different carrier frequency setting value. please find c 6~0 3 in 4.2.
the content of setting.
 1 setting value 0 .
initialization will not be executed and only go to the initialization
display.
2 setting value 1110.
to memorize the initialization set by user' but not execute.
3 setting value 2220.
2 line system initialization (the initialization of factory default).
3 setting value 3330.
3 line system initialization.
1110 user constant value restoration.
1110 (user constant value restoration) it is operation to change the inverter's constant to the initial value set by user.
110 setting value's operation: when 02-03 is 0'a l-03 is set to be 110 and press enter. then the value will be
changed to the initial value memorized by the user.








the setting of initialized value of 1110:please do according to the below processor after setting the constant
value and memorizing it: press (menu) to jump to the status selection. press(up)key  to go to environment s-
tting mode' and press (data/enter)it .adjust a l-01 (constant access level)to be "4" and go back  to the mode
selection. program mode and set 02-03 (user constant memorizing ) to be 1 and memorize it then go back to
environment setting mode set a l-03 to be 1110 and press (date/enter) to confirm. at this time' the inverter's
constant setting value will be memorized as the initial value of 1110. the constant has not been initialized and
after the operation'02-03 will go back to 0 automatically.

Wednesday 6 July 2016

VC SERIES CONTROL MODE SELECTION.OF INVERTER.

VC SERIES CONTROL MODE SELECTION.

to selection one among the 4 control modes through constant a l-
02. it can't go back to the factory setting during constant initializat-
ion. i.e' this constant can;t be initialized to change the value to be
factory default ' please set it again.
a l-0 2 the setting content.
setting 0= v/f control without pg (normal v/f control)
setting 1= v/f control with pg (v/f control which uses pg speed
control card).
setting 2= vector control without pg (the vector control which
utilizes the speed data in the inverter).
setting 3= vector control with pg ( vector control with pg speed
control card).




Tuesday 5 July 2016

THE OPERATION INTRODUCTION ON ACCESS LEVEL MODIFICATION.OF INVERTER

THE OPERATION INTRODUCTION ON ACCESS LEVEL MODIFICATION.


please find below for the introduction on how to change the access level. the status is factory default before modification. the value of
constant a l-0 2 ' constant access level is 2 . please operate as follows to change a l-02 to be 3 (normal setting) .
operation frequency ref =0.00hz press menu key to go to mode
selection status. press up key to display the next mode . press
data enter key to enter constant display status of environment sett-
ing mode. press up key to change the current constant a l-00 to a l-0 l . press data enter key to set a l-0 l . press up key to change it to be the constant value description : the " 2 " in a l-0 l (#2===)is the set
value.quick start " is the name of setting value "2" .press data enter key to confirm the modification . modification is over' the data is up-
dating . automatically return to the constant displaying status of enfir-
onment setting mode.





Monday 4 July 2016

ACCESS LEVEL OF VC SERIES CONSTANTS.OF INVERTER.

ACCESS LEVEL OF VC SERIES CONSTANTS.

this series inverter has 3 levels of access which can be set by a l -o l. the constants accessed by different access level are
different too. the quick setting access level code q and setting range 2 factory default setting 2 adjustable or not in operation is 0 the necessary constants for access and simple setting operation (factory default setting ) the normal setting
access level code b setting rang 3 factory default setting 2 and adjustable or not in operation 0 it can ready access and set basic constants.advanced setting access level code a se-
tting range 4 factory default setting 2 adjustable or not in op-eration is 0 it can access and set all the constants.
the constant quantity for quick setting' normal setting and ad-
vanced setting is different. quick setting is suitable for simple
operation application.advanced setting is suitable for higher
control requirement application.





Sunday 3 July 2016

INVERTER,S THE SWITCH AND MODIFICATION OF VC SERIES'S CONSTANTS.OF INVERTER.

THE SWITCH OF MODIFICATION OF VC SERIES'S CONSTANTS.

in the set status' press (menu) to display driving modes and then press
up and down key to go to the mode you want to enter. press (data/enter) to enter and press up and down key to display the const-ant or constant group. press (data/enter) to set the current constant or constant group to be displayed. after entering the constant group'and
press up and down key to change the display constant. press (data/
enter)and enter the constant setting status. the constant's setting is ch-
anged by up and down key. 1  t the constant value is of more than one bits' please t enter reset to move the cursor. after modifying the
constant'please press (data/enter)to complete the modification (const-
ant has been modified)' press (esc) to cancel the modification of the
current constant. (constant will not be modified). in each mode and constant display status'press (esc) to return to the previous status.for
example' to press (esc) to return to constant modifying status. another example' in the driving mode' u 1-0 2 is displayed' press (esc) to return
to mode selection status. in different constant access level' each mode
has different displayed constant. ( please find the section 3.5.3). please
below fig for the relations between and among constants' constant group
and each mode.





Tuesday 28 June 2016

THE SHIFT OF INVERTER'S CONSTANTS.

    THE SHIFT OF INVERTER'S CONSTANT

press (menu) to display the program and then press (^) to switch between the different parameters. when accessing or setting the variable constants, please enter {data/enter} return to the previous
page from the constant's read and access'please press (esc) press (data/enter) to display constant value and press it again to finish the setting.press (esc) to return to the previous status. at the factory default value (al-01=2)'i'e' the access of the constant is fast setting' the inverter's operation flow chart is as follows after it is powered on.

after the inverter is powered on' the operator's lcd screen will display the manufacturer's name and then enter the driving methods (monitor
ed constant: u constant) . it display the current frequency setting (u 1-
01 frequency command=0.00hz)' in this status'press up and down key to circularly  display the current input frequency ' output frequen-
cy' output current' output voltage and other constant which can monitored.



the access and setting of the necessary constants for operation.they
are classified as follows according to the function group.
application: it is used for operation mode selection' dc braking' spe-
ed research .
adjustment: acceleration time's characteristics. carrier frequency and
etc.
command relation: the setting of frequency command.
motor constant: v/f characteristics' motor's constant.
option constant: about the option card setting.
exterior terminal function: about the setting of plc input and output'
along value input option.
operator: operator's representation.the selection of key function.
self-learning mode: when using the motor with unknown constants in
vector control operation' the motor constant can be automatically
calculated and set.
check method: to access and set the different constants which is different from the factory default.

















Sunday 26 June 2016

OPERATING STATUS OF DRIVING MODE. OF INVERTER

             OPERATING STATUS OF DRIVING MODE.

inverter operation mode
frequency command and output current display 'inverter operation status display exception content display exception record display' etc.

operating status of program mode.

to select the display language of operator.to access the constants' to set the access level . the selection of control mode constant's initialization . adjust;
acceleration/deceleration time's curve characteristic . command relationship concerning frequency command setting . motor constant'v/f characteristic motor constant . option constant ;concerting selection card's setting . exterior terminal function; concerning the setting of switching value input and output analog value input and output . operator; operating function of operator key function selection of operator.




Friday 24 June 2016

THE OPERATOR'S LAYOUT OF INVERTER

THE OPERATOR'S LAYOUT OF INVERTER
1 constant display screen.
2 exterior input operating command indicator.
3 exterior input frequency command indicator.
4 stop indicator.
5 stop.
6 menu.
7 return.
8 increment.
 9 access.
10 shift/reset.
11 for/rev.
12 decrement.
13 jog.
14 operation mode selection key.
15 operation key.
16 operator operation indicator.
17 reverse operation indicator.
18 forward operation indicator.
19 driving mode indicator.
constant display screen.
it is 5-bit led display screen to display the function code and setting value and monitored value.
remote control indicator.
seq indicator will be lighted when circuit terminal inputs operating command ref indicator will be
when the frequency is input by control circuit terminal 13'14.
operation direction indicator.
fwd will be on in forward operation.rev will be on in reverse operation.
driving mode indicator.
the indicator is lighted only when selecting the driving mode.

  OPERATOR'S DISPLAY STATUS OF INVERTER.

when this inverter is powered on'the operator's led
screen will display the company's cod and then it
comes to the constant check method and display the current frequency setting (f) in this stats 'the current
frequency setting'output frequency setting output
current setting (a) output voltage setting (u) and other constant (u) which can be monitored will be
displayed on the screen in consequence.the key (menu) can also effect the switch over between check method (monitored constants) and program method (other operating constant).the shift of each monitored constants can be achieved by decrement'increment and shift key under the status of other di-
splayed constant (u--) access key can display and set the data. to press (esc) to return to the check m-
ethod displaying status. since the variable constants and function inverter are summarized in menu'it is e-
asy to set the constants.inverter has two power on status.





SERIES'S OPERATION KEY FUNCTION.

           SERIES'S OPERATION KEY FUNCTION.

1 operation mode selection.
used for switch over between operator control operation mode and control circuit terminal control mode.

2 menu
used to select one of the 5 modes.

3 esc
return to the previous status.

4 shift/reset
used for constant value selection when setting the constants
it is used for fault reset when fault occurs.

5 access
press this key to decide the mode' constant'setting.

6 increment
used for changing constant code and setting. (increment)

7 decrement
used for changing constant code and setting. (decrement)

8 for/rev
press this key to change the motor's speed direction when the
operation is controlled by operator.

9 run
press this key to start the inverter's operation when the inverter
is controlled by operation .run will be on at this time.

10 stop
press this key to stop the inverter's operation when the inverter
is controlled by operator. stop will will be on at this time.it can
be enable or disable by constant 02-02 when the inverter is
under terminal control.  



Wednesday 22 June 2016

DANGEROUS

                   DANGEROUS
the power input hall be input after the terminal cover is well installed. please do not destach the cover when the power is on.
if the inverter's power-failure restart function is enable'and electr-
omagnetic contactor is not installed at the input side'please keep
away from the equipment'because the inverter will be started
suddenly when the power is vailable.

                      NOTE
when braking device is installed'the high voltage discharge at the two ends of the braking resistor.it could cause electric shock or
burns.please check again the rating of the motor and other machine
before operation.it could lead to human injury.please do not check
the single during operation. it could lead to the equipment's damage.please change the inverter's setting as you wish'this series
of inverter has been set properly before shipment.it could damage
the carrier frequency needs to be set again whenever the operation of factory default reset is executed'otherwise' the inverter could be damaged.the inverter with different capacity shall be set with different carrier frequency.please find the description in c6-01-03 of 4.2.it could
lead to the damage of the inverter.  





Tuesday 21 June 2016

AC 3PHASE INVERTER,S WIRING NOTES

          WIRING NOTES

1 . when dismounting the'motor please cut off the power supply
     first.
2 . the switch over of motor or mains supply can be done only
     when inverter's output stops .
3 . when the inverter is installed with exterior devices  (barking
     unit' reactor'filter) please test the devices'resistance to the
     ground by 1000v level megameter and make sure the
     resistance is not less then 4m.
4   input command single cable and frequency meter cable need
     to be shielded'and it also should be wired separatedly.it is
     better to kept away from the main circuit connection.
5   to avoid from the wrong action caused by interference'the
     control circuiting cable shield be twisted pair cable'and the
     wiring distance shall be less the 50m.
6   please do not make shielding cable connect to the single
     cable or machine's housing.the naked wire shall be wraped by
     isolation tape.
7   all the lead wires  voltage with stand level shall be same as the inverter's voltage level.
8   to avoid of accident'control grounding terminal g must be well connected to the ground.the grounding wire      cann't be the other equipment's grounding wire.the grounding wire specification shall be bigger then half of
     the above-said wire specification.when the wiring is completed'please check whether there is cable'screw
     or connector lug left in the equipment or not'whether the screw is loose 'whether the naked wire of the
     terminal is short-circuited to the other terminal.  




     

Sunday 19 June 2016

AC 3PHASE INVERTER,S CONTROL CIRCUIT TERMINAL WIRING DESCRIPTION





















CONTROL CIRCUIT TERMINAL WIRING DESCRIPTION.

to reduce the control signal's interference and attenuation' the control signal's wiring length shell be limited within 50 cm and the distance to the power cord shell be longer than 30 cm. when connecting the along input and output signal' please use twisted pair cable and connect one end of the shielding sleeve to the ground.

CONTROL CIRCUIT CONNECTION NOTES.

to layout separatedly the control circuit cable'main circuit cable and other power supply cable. to avoid from
the wrong operation cased by interference' control circuit cable needs to be twisted pair cable. the connection distance shall be less than 50 m. the distance to power cable needs to be more than 30 cm. please use twisted pair cable for the command from terminal. please see below when the output contact of multifunction  optical coupler connects to relay' coil's two ends needs to connect to bypass diode in parallel.
please do not make shielding cable connect to the single cable or machine's housing. the naked wire shall be
wraped by isolation tape.
contact output terminal 9'10'18'19'20' must be connected to terminal 1~8'11~17'21~23'25~27'33 independently.  



    

Saturday 18 June 2016

AC 3PHASE INVERTER,S CONDUCTION INTERFERENCE PREVENTION METHOD.



















CONDUCTION INTERFERENCE PREVENTION METHOD.

to suppress the conduction interference from the output side' it is applicable to let all the input cables go through a grounded metal tube.







THE WIRING DISTANCE BETWEEN INVERTER AND MOTOR.

the longer the wiring distance between the inverterand motor is' the higher there carrier frequency is and the  gigger the upper harmonics current in the cable is . the current leakage will implement bad effect on the embient equipment . in this case it is necessary to minimize the current leakage. please find below table for the relation between the wiring distance (between the inverter and motor ) and carrier frequency .

Tuesday 14 June 2016

AC 3PHASE INVERTER,S PHASE-SHIFT CAPACITOR IS NOT ALLOWED TO USE.OF INVERTER.

















please do not connect phase-shift capacitor or lc/rc filter to the output circuit. otherwise'the inverter will
be burned.






ELECTROMAGNETIC SWITCH BETWEEN INVERTER AND MOTOR IS ALLOWED TO USE.
please do not connect electromagnetic switch'electromagnetic contactor to the output circuit.otherwise'
the inverter's surging current will lead to the action of over current protection. in serious case'the inverter's
internal parts could be damaged.

please install a mccb which is compatible to the inverter' capacity .

1  . the capacity of mccb should be 1.5-2 multiples of the inverter's rated current . mccb's time characterics
shall satisfy the inverter's overload protection characteristics (150% of the rated current /minute' 180% of the rated current/2 second )

2  . when mccb is shared by two or above motors or other equipment ' please connect according to the below fig . connect the fault output relay contact of the inverter to the power supply contactor and cut off the
input power supply .

THE INSTALLATION AND SELECTION OF ELECTROMAGNETIC CONTACTOR.
to cut the main circuit power supply at the fault of inveryer and prevent the inverter from restarting at fault' please install electromagnetic contactor on the power supply side of the inverter.

RFI PREVETION  SOLUTION.
input cable'output cable and the inverter itself all can create fri. dedicated filter needs to be used at both input
side and output side of the inverter. the normal filter cann't achieve the expected effected. and the input and output terminal shell be custom-made. the rfi can be reduced to use iron device for shielding the connecting
cable between inverter and motor shall be as short as possible. please find below for the rfi prevention.




Monday 25 April 2016

AC 3PHASE INVERTER,S MAIN CIRCUIT CONNECTING METHOD .

























INVERTER (main circuit connecting method )


at run time' please check whether the motor is in forward operation
at the command of forward operation . if it is in reverse operation'
please stop the system' cut the power supply and exchange any two
terminals among  u'v'w  then the motor will run forward .
do not disconnect the power supply to the inverter's output terminal '
otherwise' the inverter's interior will be damage. the grounding of
output terminal is not permitted. please do not left the output cable
to touch or connect the machine housing'otherwise'the inverter's
interior could be damage.

please do make sure the grounding wire connects to the ground. the grounding resistor resistance should be
less than 10w for inverter of 380 v  level .
welding machine or other power equipment . the wire diameter shall conform with the stipulation of electric
equipment technical standard' and the wire should be as short as possible . in the occasion where two inverters are used at the same time' please do not make the grounding wire establish a loop. please find below for the correct grounding method and the wrong grounding method.
note; do not grounding the neutral point of the motor with y  connection.



Friday 22 April 2016

ELECTRIC INVERTER,S {to select ac reactor }





















                     INVERTER {to select ac reactor }


when the inverter works in the big power circuit'since the power supply's
impedance is small' the input rectifier will create big peak current.
this phenomenon is becoming more serious when there is capacitor over
compensation in power supply' or the circuit is connected to big power
rectifier or when static condenser is switching.to improve the above situation'
please select an ac reactor according to the range shown in below fib






   power capacity(kva)
                                    --- - - - -----------------------------
      400                        - ac.choke coil or                --                            
                                   -  dc.reactor is.                 -                      
                                   -  necessary                  -                
     600                              -                         -      
                                    ---------------------                          
                                     -------------------------------------
             0                                            60                   400

                                            inverter power (kva)

INVERTER (the selection of radio noise filter )



when the radio interference is serious to the exterior or the
exterior radio interference is serious to the inverter please
use radio noise filter to reduce the two way interference
caused by radiation or conduction.











 

Thursday 21 April 2016

AC 3PHASE INVERTER,S {TERMINAL FUNCTION OF MAIN CIRCUIT }







      INVERTER{terminal function of main circuit}

input power supply: r  s  t
grounding cable: g
DC bus:   -    +
motor wiring: u  v  w
braking resistor: pb

the main circuit terminal function is shown as below table.conduct correct wiring
according to the corresponding functions.


TERMINAL CODE                                FUNCTION DESCRIPTION

r s t                                         power supply input terminal ' it connects to 3- phase ac power supply or                                                single phase ac power supply.


u v w                                     are inverter's output terminal.it connects to 3 phase ac motor


-  +                                        connects to the connecting terminal of braking unit. - + they are
                                             respectively the dc bus's anode and cathode.


+, pb                                     braking  resistor connecting terminal.one end of the resistor connects to
                                             +; the other end connects to pb



G                                        g grounding terminal;connecting to the grounding.



exterior devices and optional parts

description of mccb

used to rapidly cut off the inverter's power supply and prevent the inverter and its circuit's
a fault from causing power supply fault.

description of  mc

at the fault of inverte's it is used to cur off the main power supply and avoid of restarting
following power failure or inverter  fault.

description of acl

it is used to improve the input power factory and reduce upper harmonics and restrict the
power supply's surging.

description of nf

it is used to reduce the radio interference caused by inerter. when the wiring distance
between motor and inverter is below  20 meters' it is recommended to connect to the
power supply side.when the wiring distance between motor and inverter is above 20
meters' it is recommended to connect to the output side.

description of  r* ub*

it is used when the braking torque cannot meet the requirement. it is suitable for the
occasion with large initial load and frequent braking fast stop.






















                                       

Wednesday 20 April 2016

INVERTER

         INVERTER

preface

chapter 1 checking

1 checking items
2 date on nameplate
3 model no description

chapter 2 installation warning

1 dimention(see appendix 2 )
2 configuration
3 installation
3.1 installation site
3.2 precautions
4 installation direction and space
5 main circuit connecting description wiring
5.1 main circuit terminal layout
5.2 terminal function of main circuit
5.3 the wiring between main circuit peripheral devices and optional parts
6 control circuit terminal wiring description
6.1control circuit terminal layout and function
6.2 control circuit connection notes
7 wiring notes


chapter 3 operation

1 the operator's function and operation of win-va
1.1 win-va series'8 operation key function
1.2 the operator's layout of win-va

2 the introduction of menu of win-va
2.1 operator;s display status of win-va
2.2 the shift of va's constants
2.3 access level of win-va series's constant
 2.4 win-va series's control mode selection
2.5 initialization

3win-va's trial operation
3.1 check point before operation
3.2 operation mode selection
3.3 to execute trial operation by operator

INVERTER{CHAPTER 4 +5+6 CONSTANTS DESCRIPTION}


4.1 menu method and layout
4.2 constant function introduction








CHAPTER{5 PROTECTION FUNCTION}

5.1 exception analysis
5.2 alarm diagnosis
5.3 operation error
5.4 fault analysis

CHAPTER{6 MAINTENANCE AND REPAIRING }

6.1 daily check and periodical check
6.2 the selection of output reactor of inverter
6.3 current leakage protector
6.4 consideration of selecting motor
6.5 the parts which  needs to be replace periodicly

6.6 storage and custody


   INVERTER {CHAPTER 1 CHECKING }

note '  do not install the inverter which is damaged or in short of parts.
it could lead to injury.
unexpected case could happen during transparation 'please do check
the products carefull before use this products has been checked strictly
before use.

CHECKING ITEMS

content to be checked

whether the content of the nameplate confirms with the products before
use
check whether there is damaged parts
check whether the screws or fastening parts get loose or not.
manual' pass sticker and other parts.

preface

chapter 1 checking

1 checking items
2 date on nameplate
3 model no description

chapter 2 installation warning

1 dimention(see appendix 2 )
2 configuration
3 installation
3.1 installation site
3.2 precautions
4 installation direction and space
5 main circuit connecting description wiring
5.1 main circuit terminal layout
5.2 terminal function of main circuit
5.3 the wiring between main circuit peripheral devices and optional parts
6 control circuit terminal wiring description
6.1control circuit terminal layout and function
6.2 control circuit connection notes
7 wiring notes

  INVERTER{MAIN CIRCUIT CONNECTING DESCRIPTION WIRING}

dangerous

please make sure the power supplier is cut offer before wiring.and do not wire or
dismantle the inverter when the power is on.
electric shock or fire dizaster could  could happen.the inverter could be damage
the wiring shall be done by the professional electric engineer.electric shock or
fire dizaster could happen.
grounding terminal should br well connected to the ground.electric shock or fire
dizaster could happen.
when emergency stop terminal is connected' please do check whether the action
is effective or not.
human injury could happen.{hte user shall take the connecting responsibility}
please do not touch the output terminal with naked hands.electric shock or
short-circuit could happen. the inverter could be damage.
























                                                                                                                                                                   